Supports EtherCAT protocol, 8-port, and IO-Link Master、Class A、006B31

Supports EtherCAT protocol, 8-port, and IO-Link Master、Class A、006B31

Order code: 006B31
Order number: FNI ECT-506-105-M
  • IO-Link M12 Hub 16×DI PNP(Figure 1)
  • Up to eight IO-Link devices can be connected
  • Integrated EtherCAT fieldbus interface
  • Protection Level: IP 67 (when properly connected)
  • Wide operating temperature range: -25...+70℃
  • Shell material: nickel-plated Gd-Zn alloy
收藏 询盘

Relevant recommendation

  • Functional parameter
  • Resource download
  • Related accessory




Technical data

Network protocolEtherCAT
Rated working voltage UB18...30V DC
Current consumption of the module≤ 130mA
Auxiliary input/output power statusUS/UA
Module status indicator
Network status indicator
Port status indicatorRed, yellow
Connection: FieldbusM12, D-coded, female
Connection: AUX power supplyM12, L-coded, male/female
Connection: I/O portM12, A-coded, female
Number of I/O ports8
Input quantityUp to 16 PNP inputs
Output quantityUp to 8 PNP outputs
Input/output configurable
Maximum load current, sensor/channel200mA
Maximum output load current2A
Port Status indicator (Signal status)Yellow LED indicator
Port diagnostic indicator (Overload)Red LED indicator
Total current Uactuator≤ 16A
Total current Usensor≤ 16A
Protection level in accordance with IEC 60529IP67 (when properly connected)
Operating temperature-25...+70℃
Storage temperature-25...+85℃
fastener2 mounting holes
Dimensions (L × W × H)223×65×25.8 mm
Shell materialNickel-plated Gd-Zn alloy
重量-





IO-Link data

IO-Link Master8×IO-Link
IO-Link version1.1
Port levelClass A
IO-Link Indicates the primary port0...3 ports for input/output devices, 4...7 Port connects only to input devices
Working mode (3 lines)SIO, COM 1, COM 2, COM 3
Indicator light communicationGreen LED indicator
Indicator light errorRed LED indicator
Maximum load current of the IO-Link device2A


specification

  • 006B31 (FNI ECT-506-105-M) - Specifications

    2024-07-31   442.84KB

Operation manual

  • 006B31 (FNI ECT-506-105-M) - Instructions

    2024-07-31   3.69MB

EPLAN

  • 006B31 (FNI ECT-506-105-M) -EPLAN (电气图)

    2023-12-01   424.67KB

Configuration file

  • 006B31 (FNI ECT-506-105-M) -ESI (Configuration file)

    2023-12-01   8.44KB

2D digital module

  • 006B31 (FNI ECT-506-105-M) -2D (DWG file)

    2023-12-11   538.88KB

3D digital module

  • 006B31 (FNI ECT-506-105-M) -3D (STEP file)

    2023-12-11   1.46MB

Relevant certificate

  • 006B31 (FNI ECT-506-105-M) -CE certificate

    2024-01-08   228.62KB

Relevant certificate

  • 006B31 (FNI ECT-506-105-M) -ROHS test report

    2024-01-17   4MB